Air Cooled Water Chiller / Heat Pump
Free-cooling Air Cooled Water Chiller
Duty: Free cooling only mode
High energy efficient chillers with free cooling system, scroll compressors, and plate heat exchanger, designed to meet demands in the commercial and industrial sectors.
Free cooling units meet growing demands for energy savings, since they have been designed to reduce the operating costs of refrigerating machines that work to serve process applications or in the IT field.
A strong point of our free cooling units is certainly the control system that allows maximum use to be made of the free resource, consisting of outside air, so minimizing the energy used by the compressors. The controller of the unit activates the chiller section and the free cooling section, also in combined mode, based on the actual external air temperatures, the set point and the required load level.
The free cooling section is hydraulically in series with the evaporator and this allows a benefit to be obtained from its activation even when the outside air temperature is sufficient to carry out only a pre-cooling of the water. The missing amount of capacity, in any case lower than the total required, will be provided by the compressors.
As the outside air temperature goes down, the amount of capacity that the free cooling section will be able to transfer to the water will gradually increase. Consequently, the amount of capacity that will have to be covered by the compressors will always be lower.
When the Total Free-cooling Temperature is reached, the free cooling section will be able to fully meet the cooling capacity requirement and therefore the compressors can be switched off. In this condition, the unit will be able to provide the system with a cooling capacity equal to that required at design conditions, but with current drawn by the fans alone.
When the ambient temperature is higher than the temperature of the water returning from the system, all the required cooling capacity must be produced by the compressors.
The total cooling capacity is generated by the compressors of the chiller section, and the free cooling coil and relevant fans remain inactive. The operation of the unit is that of a classic chiller.
The 3-way valve bypasses the free cooling coil (so preventing unnecessary head losses) and condensation control is done, when necessary, through fan speed modulation.
When the ambient temperature is lower than the temperature of the water returning from the system, the controller activates the free cooling section.
The control switches over the 3-way valve to put the free cooling coil in series with the evaporator and with the free cooling section fans.
The water leaving the free cooling coil will be "pre-cooled" by the outside air (partial free cooling) and is sent to the evaporator inlet. Now the chiller section can operate in reduced capacity mode because it will have to produce only the amount needed to reach total cooling capacity.
For outside air temperatures lower than or equal to the Total Free-cooling Temperature, the unit operates exclusively in free cooling mode.
The output capacity from the water coil fully meets the demand of the system, and therefore the condensing section fans are completely switched off and so are the compressors.
As the outside air temperature falls, the output capacity from the free cooling section will gradually increase and therefore the control of the unit will modulate performance either through stepped management of the fans (standard management) or through fan speed modulation for units that adopt EC fans for the free cooling section.
More from Air Cooled Water Chiller / Heat Pump

Mini Air Cooled Water Chiller
The mini series air cooled water chiller/heat pump is an effective all-in-one package that is easy to install and maintain
View specifications →
Modular Air Cooled Scroll Chiller
The modular series air cooled water chiller/heat pump is an effective all-in-one package that is easy to install and maintain
View specifications →
Big Air Cooled Scroll Chiller
The modular series air cooled water chiller/heat pump is an effective all-in-one package that is easy to install and maintain